SPECIFICATION SUBMITTAL
369-401a 22 2.3.11
GP Dimming Panels
GRAFIK Systems
®
•Surfacemountindoors.
•Panelgeneratesheat.Mountonlywhereambient
temperaturewillbe0-40°C(32-104°F).
•Thisequipmentisaircooled.Donotblockvents
or warranty will be void. Leave 12 in (310 mm)
clearances above, below, and in front of Panel.
No clearance necessary on sides.
•Reinforcewallstructureforweightandlocalcodes.
Wiring Raceway
Load
Circuit
Wiring
Feed
Wiring
Branch
Circuit
Breakers
Terminal
Blocks
for Load
Circuits
NEC
® Class
2/PELV
Wiring
12 in
(310 mm)
minimum
12 in
(310 mm)
minimum
top and
front
GP3/4 Front View GP3/4 Side View
For maximum Feed and Wire Sizes,
consult Wiring Overview page.
•DimmingPanelswillhumslightlyandinternalrelayswillclick
while in op er a tion. Mount where audible noise is ac cept able.
•MountPanelssoline(mains)voltagewiringisatleast6ft
(1.8 m) from sound or electronic equipment and wiring.
•GPPanelsmustbemountedwithin7°oftruevertical.
GP3/4 Mini Panel Mounting
Panel
GP3/4
Maximum
BTUs/Hour
685
Weight
(withoutpackaging)
30lbs(14kg)
Notice: Water damages Panels. Install where they will not get wet.